- CTs must be installed inside an approved CT cabinet (examples below) and may not be installed inside a single-phase pad transformer.
- The customer (or their electrician) must supply the CT cabinet with CT landing platform, and the meter socket.
- Current transformers, meter, and wiring are provided by Clearwater Power.
- The CT can should be installed on the customer's building or a Unistrut system within 10-feet of the transformer (never mounted to the utility pole).
Single Phase CT Cabinet Details
- Single-phase CT Cabinet with Landing Platforms: 400A
- Eaton B-Line: 363611RTCT (6019 HAL)
- Milbank: CT363611SC (K4903)
- Hoffman: A363611CT
- Single-phase CT Cabinet with Landing Platforms: 600-800A
- Eaton B-Line: 364811HRTCT (6019 HEL)
- Milbank: CT364811HC (K4729)
- Hoffman: A483611HCT
- Single-phase, 6-Terminal, Meter Socket
- Eaton B-Line: U121315-50365
- Eaton B-Line: 12146
- Milbank: U3540XL Plus (2) 5T8K2