Standards of Service

Three-phase CT Installation (for accounts with a service larger than 200-amps)
  • CTs must be installed in an approved cabinet (examples below)
  • The customer (or their electrician) must supply the CT cabinet with CT landing platform, and meter cabinet.
  • Current transformers, meter, and wiring are provided by Clearwater Power.
    Three-Phase CT Cabinet Details
    • Three-phase CT Cabinet with Landing Platforms: 201-800A
      • Eaton B-Line: 364811HRTCT (6067 HEEL)
      • Milbank: CT364811HC (K4722)
      • Hoffman: A483611HCT
    • Three-phase CT Cabinet with Landing Platforms: 801-1200A
      • Hoffman: A1200NECT (48"x48"x12")
    • Three-phase, A-Base Meter Cabinet
      • Milbank: 243011-TC3R-WB
Single-Phase CT Installation (for accounts with a service larger than 400-amps)
  • CTs must be installed inside an approved CT cabinet (examples below) and may not be installed inside a single-phase pad transformer.
  • The customer (or their electrician) must supply the CT cabinet with CT landing platform, and the meter socket.
  • Current transformers, meter, and wiring are provided by Clearwater Power.
  • The CT can should be installed on the customer's building or a Unistrut system within 10-feet of the transformer (never mounted to the utility pole).
    Single Phase CT Cabinet Details
    • Single-phase CT Cabinet with Landing Platforms: 400A
      • Eaton B-Line: 363611RTCT (6019 HAL)
      • Milbank: CT363611SC (K4903)
      • Hoffman: A363611CT
    • Single-phase CT Cabinet with Landing Platforms: 600-800A
      • Eaton B-Line: 364811HRTCT (6019 HEL)
      • Milbank: CT364811HC (K4729)
      • Hoffman: A483611HCT
    • Single-phase, 6-Terminal, Meter Socket
      • Eaton B-Line: U121315-50365
      • Eaton B-Line: 12146
      • Milbank: U3540XL Plus (2) 5T8K2
Stacked Loops

We do not allow single stack loops. Load and source must have their own separate conduits. If Clearwater Power is asked to perform a disconnect, our crew will not reconnect service until they are separated.

Secondary Wiring

No bare-wire secondary is allowed. If Clearwater Power is asked to perform a disconnect, our crew will not reconnect service until the bare wire is removed from any Clearwater Power equipment.

Pole Attachments

Clearwater Power does not permit any attachments of any kind to any power poles other than contracted joint-use agreements with other utilities. This includes yard lights, fences, gates, etc. If you are a telecom provider seeking a joint-use agreement, please contact our engineering department before performing any work or obtain the necessary easements.

Meter Bases

Meter bases cannot be attached to a primary pole or transformer pole. Existing meter bases may currently be attached to a transformer pole. This is allowable unless a disconnect/reconnect is requested. Clearwater Power will perform a disconnect, however, will not be able to reconnect until the meter base is moved to an approved meter pedestal or meter pole.

Visual Example of Approved Meter Bases